Ammonia Pipe Marking Guide: IIAR Bulletin #114

How ammonia refrigeration piping and components are identified under IIAR Bulletin #114: what each part of the marker means, the system abbreviations, marker sizes and where markers go.

What Bulletin #114 is

IIAR Bulletin #114, Guideline for Identification of Ammonia Refrigeration Piping and System Components, was developed and published in 1991 by the International Institute of Ammonia Refrigeration to establish uniformity among ammonia refrigeration users in identifying refrigerant piping.

The guideline was based on ANSI Standard A13.1-1981, Scheme for Identification of Piping Systems. That standard was further revised in 2020 and included a change from a yellow background to an orange background for toxic and corrosive fluids. Bulletin #114 updates the IIAR standard to reflect the ASME changes and provide better consistency with general industry standards.

  • The use of color to identify fluid characteristics is suggested and adopted by the bulletin in an effort to bring consistency to the industry and aid in training and safety efforts.
  • The suggested color scheme is not intended to replace existing color schemes that have been established by facilities.
Orange or yellow? Orange is the background in the updated bulletin. Craftmark ammonia markers are available in orange or yellow, so you can match the markers already in your facility.

Scope

The bulletin establishes guidelines for identifying piping in a closed-circuit ammonia refrigeration system, as well as related refrigeration system components.

  • All piping mains, headers and branches should be identified as to the physical state of the refrigerant (vapor, liquid, etc.), the relative pressure level and the direction of flow.
  • All refrigerant system components should also be uniformly identified: compressors and compressor units, condensers, receivers, thermosyphon vessels, recirculators, intercoolers, accumulators, transfer vessels, oil pots, evaporators, heat exchangers and any other component of the system containing refrigerant.

Reading an ammonia pipe marker

A marker identifies the refrigerant in that piping segment, including its physical state, relative pressure level and direction of flow. Each marker has five sections.

MTRSLIQVAPAMMONIALOWABCDE
  • APiping abbreviation. The IIAR system abbreviation, in black letters on an orange background.
  • BPhysical state. LIQ in black letters on a yellow band and/or VAP in black letters on a baby blue band.
  • CAmmonia. The word AMMONIA in black letters on an orange background.
  • DPressure level. Under 70 psig is low pressure: the word LOW in black letters on a green band. Over 70 psig is high pressure: the word HIGH in black letters on a red band.
  • EDirection of flow. A black arrow on the orange background, scored for use in either direction. On vinyl snap-on markers the arrows and legend are printed universally, so the arrows point the right way however the marker is positioned.

System abbreviations

The IIAR abbreviations, with the physical state and pressure level printed on the stock marker for each.

IIAR abbrev.SystemPhysical statePressure level
BDBooster DischargeVAPLOW
BSBooster SuctionVAPLOW
CDCondenser DrainLIQHIGH
DCDefrost CondensateLIQHIGH
ESEconomizer SuctionVAPLOW
EQEqualizerVAPHIGH
FGFoul GasVAPLOW
HPLHigh Pressure LiquidLIQHIGH
HSDHigh Stage DischargeVAPHIGH
HSSHigh Stage SuctionVAPLOW
HTRLHigh Temperature Recirculated LiquidLIQLOW
HTRSHigh Temperature Recirculated SuctionLIQVAPLOW
HTSHigh Temperature SuctionVAPLOW
HGHot GasVAPHIGH
HGDHot Gas DefrostVAPHIGH
IPLIntermediate Pressure LiquidLIQHIGH
LDLiquid DrainLIQLOW
LICLiquid Injection CoolingLIQHIGH
LTLiquid TransferLIQLOW
LSSLow Stage SuctionVAPLOW
LTRLLow Temperature Recirculated LiquidLIQLOW
LTRSLow Temperature Recirculated SuctionLIQVAPLOW
LTSLow Temperature SuctionVAPLOW
MTRLMedium Temperature Recirculated LiquidLIQLOW
MTRSMedium Temperature Recirculated SuctionLIQVAPLOW
MTSMedium Temperature SuctionVAPLOW
ODOil Drain——
POPump OutLIQLOW
PUPurgeLIQHIGH
PLPurge LineVAPHIGH
RVRelief Vent——
RVRelief VentVAPHIGH
TSRThermosyphon ReturnLIQVAPHIGH
TSSThermosyphon SupplyLIQHIGH
TSVThermosyphon VentVAPHIGH

Relief Vent (RV) is stocked two ways: with VAP / HIGH bands, and with no state or pressure bands.

Marker dimensions and lettering size

IIAR Bulletin #114, Section 4.1.8. Pick the marker by the outside diameter of the pipe, including insulation.

Pipe diameter (O.D.)Marker widthMarker lengthLetter sizePhysical statePressure levelColdMark™ style
Up to 1.25"1"8".5".5".5"AR1
Over 1.25" to 2"1.5"8".75".75".75"AR2
Over 2" to 7"2.5"12"1.25"1"1"AR3
Over 7" to 10"3.5"24"2.5"1.5"1.5"AR4
Over 10"4.5"32"3.5"2"2"AR5

Marker material requirements

  • Pipe markers may be of the self-adhesive, snap-on or strap-on type. Choose the type of marker system that best suits the area of use.
  • Prepare the pipe surface. Thoroughly degrease, clean and dry the pipe before installing a self-stick marker, to avoid trapping moisture, which can cause corrosion on uninsulated piping systems.
  • Markers should resist fading from indoor and outdoor ultraviolet (UV) or infrared radiation.
  • Markers must be suitable for application to insulated or non-insulated piping.
  • Self-stick markers must have an adhesive backing that adheres in all temperature ranges served by the refrigeration system and retains its adhesive qualities when applied to outdoor piping.

Component markers

Component markers bear the name of the equipment they identify, such as RECEIVER, ACCUMULATOR or RECIRCULATOR, along with a pressure level designation.

ACCUMULATORLOW

3.5" wide and up to 32" long, with 2.5" tall lettering.

  • Black letters on an orange background.
  • Pressure level is shown by the word HIGH in red letters (over 70 psig) or LOW in green letters (70 psig or less) on the far right-hand side of the marker.
  • Component markers are 3.5" wide by up to 32" long, to accommodate the name of the component.
  • Lettering is 2.5" tall.
  • Self-stick markers follow the same material guidelines as the ammonia pipe markers.

Where to place markers

Simplified location and usage guidelines.

Roads and waterwaysWhere pipelines pass over or under a road or waterway, apply a marker and arrow on both sides of the road or waterway.
Above or below the line of visionIf pipelines are above or below the normal line of vision, place markers below or above the horizontal centerline of the pipe so they can be read.
WallsWhere pipelines pass through a wall, apply a marker and arrow on the pipe both entering and exiting the wall.
Risers and T-jointsPlace a marker and arrow on each riser and T-joint, with arrows pointing away from the legend.
ValvesApply a marker and arrow either entering or exiting a valve to show contents and direction of flow.
Reference chartsPost a reference chart that explains the markers and abbreviations where operating and repair personnel will see it. Make it of durable material and replace it when it is damaged or no longer legible.